4th Edition Wiring Rules Notes

E-mail Print

Height of socket outlets The heights specified in Clause 554 should not apply to dedicated sockets for appliances (eg. cooker hood, extractor fans or plasma TV’s in pubs) that are left plugged in etc.

Height of thermostat control devices There is an optimum height at which the thermostat is most effective and this should be adhered to in accordance with manufacturer’s instructions.
RCD Separate

 

RCD is not required in bathroom, but more than one is desirable.

Isolation of inaccessible sockets (eg in Kitchen) A single switch for all sockets is not acceptable. What is required is a switch for each single or double socket that is not accessible.

Main MCB in meter cabinet An independent IP55 enclosure to house the MCB within the meter cabinet is essential. This is in case the meter cabinet is left open.

Wet Rooms These are treated in the same manner as locations containing bath or shower.

Micro Generators The requirements in Ireland differ from those in the UK. They must be on a dedicated circuit and any associated RCD must be 2 pole (single phase).